![Stober 56690 Manual Download Page 138](http://html.mh-extra.com/html/stober/56690/56690_manual_1381233138.webp)
12 | Diagnostics
STOBER
138
05/2019 | ID 442790.01
12.2.4
Event 33: Overcurrent
The drive controller is interrupted if:
§
U30 = 0: Inactive
Response:
§
The power unit is disabled and axis movement is no longer controlled by the drive controller
§
The brakes are no longer controlled by the drive controller and engage in the event of an inactive release override
(F06)
The drive controller is interrupted with emergency braking if:
§
U30 = 1: Active and
§
A29 = 1: Active for STOBER device controller
or
§
U30 = 1: Active and
§
A540 = 2: slow down on quick stop ramp for CiA 402 device controller
Response:
§
The axis is stopped by emergency braking; the brakes are no longer controlled by the drive controller and engage in the
event of an inactive release override (F06)
§
At the end of emergency braking, the power unit is disabled and axis movement is no longer controlled by the drive
controller
Cause
Check and action
Short acceleration times
Check the actual current using the scope image and reduce the acceleration values if
necessary (E00)
Large torque/force limits
Check the actual current using the scope image (E00) and reduce the torque/force
limits if necessary (C03, C05)
Wrong drive controller design
Check the design and change the drive controller type if necessary
Tab. 150: Event 33 – Causes and actions