9 | Connection
STOBER
96
05/2019 | ID 442790.01
9.4.20
X300: Brake 24 V supply
X300 is used to supply the brake.
ATTENTION!
Device damage due to overload!
If the 24 V
DC
power supply is looped to multiple devices over the terminal, the terminal may be damaged by a current that is
too high.
▪
Make sure that the current over the terminal does not exceed the value 15 A (UL: 10 A).
Electrical data
Single-axis controller
Double-axis controller
U
1
+24 V
DC
, +25%/−0%
I
1max
2.5 A
2 × 2.5 A
Tab. 99: Electrical data of the control unit brake control
Pin
Designation
Function
1 | 3
2 | 4
1
+
24 V
DC
supply for the brake; bridged in the terminal;
design in accordance with EN 60204: PELV, secondary
grounded, recommended fuse protection: max.
15 AT
12
2
3
−
Reference potential for power supply voltage of the
brake
4
Tab. 100: X300 connection description
For connecting wiring, observe the terminal specifications in the chapter
Cable requirements
Feature
All sizes
Max. cable length
30 m
Tab. 101: Cable length [m]
9.4.21
X700: SD slot
The SD slot is used for data backup in the case of service. SD and SDHC cards with storage capacity from 128 MB to 32 GB
are supported. SDHC cards with a storage capacity of 64 GB can be used only if they have been first reformatted to max.
32 GB. Since higher capacities increase the controller starting time, STOBER recommends the use of cards with a storage
capacity from 2 to 4 GB.
Information
The drive controller has internal configuration memory and can therefore be operated without an inserted SD card. In the
DriveControlSuite commissioning software, the action A00 Save values always saves to both the internal configuration
memory and the inserted SD card. Back up your configuration to an SD card after completing commissioning in order to
allow transfer of the configuration to the replacement controller in the case of service. When the replacement controller is
switched on, the data is loaded with priority given to the inserted SD card. To make a non-volatile back-up in the internal
configuration memory, you must run A00 Save values.
12
For UL-compliance, use of a 10 A fuse (time delay) is required. Be sure that the fuse meets certification requirements for
DC voltage in accordance with UL 248.