12 | Diagnostics
05/2019 | ID 442790.01
155
12.2.21
Event 53: Limit switch
The drive controller is interrupted if:
§
A29 = 0: Inactive for STOBER device controller
or
§
A540 = 0: disable drive, motor is free to rotate for CiA device controller
Response:
§
The power unit is disabled and axis movement is no longer controlled by the drive controller
§
The brakes are no longer controlled by the drive controller and engage in the event of an inactive release override
(F06)
The drive controller is interrupted with a quick stop if:
§
A29 = 1: Active for STOBER device controller
or
§
A540 = 2: slow down on quick stop ramp for CiA device controller
Response:
§
The axis is stopped by a quick stop; meanwhile, the brakes are controlled by the drive controller and remain released
§
At the end of the quick stop, the power unit is disabled and axis movement is no longer controlled by the drive
controller; the brakes are no longer controlled by the drive controller and engage in the event of an inactive release
override (F06)
Number
Cause
Check and action
1: Hardware-Limit-Switch
positive
–
2: Hardware-Limit-Switch
negative
End of the travel range
reached
Move in the travel range in the direction opposite the limit
switch
Connection error
Check the connection and source parameters and correct
them if necessary (I101, I102)
Defective connection cable
Check the cable and replace it if necessary
3: SW-limit switch
positive
–
4: SW-limit switch
negative
End of the travel range
reached
Move in the travel range in the direction opposite the limit
switch
Travel range too small
Check the positions of the software limit switches and correct
them if necessary (STOBERI50, I51 or CiA A570[0], A570[1])
5: +/- 31 bit computing
limit reached
Computing limit of the data
type reached
Check the command sequences for multiple successive
commands without a breakpoint 3: MC_MoveAdditive and the
number of decimal places of the axis model and reduce them
if necessary (I06)
7: Both limit switches not
connected
Connection error
Check the connection and source parameters and correct
them if necessary (I101, I102)
Defective connection cable
Check the cable and replace it if necessary
Tab. 167: Event 53 – Causes and actions