9 | Connection
05/2019 | ID 442790.01
87
9.4.10
X11: 24 V supply
The connection of 24 V
DC
to X11 is required for the power supply of the control unit.
ATTENTION!
Device damage due to overload!
If the 24 V
DC
power supply is looped to multiple devices over the terminal, the terminal may be damaged by a current that is
too high.
▪
Make sure that the current over the terminal does not exceed the value 15 A (UL: 10 A).
Electrical data
All types
U
1CU
24 V
DC
, +20%/−15%
I
1maxCU
0.5 A
Tab. 77: Control unit electrical data
Pin
Designation
Function
1 | 3
2 | 4
1
+
24 V
DC
supply for the control unit; bridged in the
terminal; design in accordance with EN 60204: PELV,
secondary grounded, recommended fuse protection:
max. 15 AT
10
2
3
−
Reference potential for +24 V
DC
, bridged in the
terminal
4
Tab. 78: X11 connection description
Information
The device may not be connected to a DC supply grid. Instead, supply it over a local 24 V
DC
power supply.
For connecting wiring, observe the terminal specifications in the chapter
Cable requirements
Feature
All sizes
Max. cable length
30 m
Tab. 79: Cable length [m]
10
For UL-compliance, use of a 10 A fuse (time delay) is required. Be sure that the fuse meets certification requirements for
DC voltage in accordance with UL 248.