12 | Diagnostics
STOBER
150
05/2019 | ID 442790.01
12.2.16
Event 46: Low voltage
The possible effects depend on the configured level (U00):
§
0: Inactive
§
1: Message
§
2: Warning
§
3: Fault
The drive controller is interrupted if:
§
A29 = 0: Inactive for STOBER device controller
or
§
A540 = 0: disable drive, motor is free to rotate for CiA device controller
Response:
§
The power unit is disabled and axis movement is no longer controlled by the drive controller
§
The brakes are no longer controlled by the drive controller and engage in the event of an inactive release override
(F06)
The drive controller is interrupted with a quick stop if:
§
A29 = 1: Active for STOBER device controller
or
§
A540 = 2: slow down on quick stop ramp for CiA device controller
Response:
§
The axis is stopped by a quick stop; meanwhile, the brakes are controlled by the drive controller and remain released
§
At the end of the quick stop, the power unit is disabled and axis movement is no longer controlled by the drive
controller; the brakes are no longer controlled by the drive controller and engage in the event of an inactive release
override (F06)
Cause
Check and action
Supply voltage does not
correspond to the configured
supply voltage
Check the supply voltage, parameterized supply voltage and undervoltage limit and
correct them if necessary (A36, A35)
Supply voltage below undervoltage
limit
Check undervoltage limit and correct it if necessary (A35)
Tab. 162: Event 46 – Causes and actions