Appendix C
DC Power Supply Model
C-3
FIGURE C-1
View of DC Power Cords
The DC power cord has a connector only for the server end. Therefore, a terminal
matching the DC power supply equipment will need to be attached to the DC power
supply end of the cord.
C.1.3
Facility Power Requirements
The power supply that can be used with the M3000 server is restricted to DC power
supply equipment that is separate from the AC power, or DC power supply
equipment that has double or reinforced insulation for high, dangerous voltages.
Always mount overcurrent protective devices between the DC power supply
equipment and the M3000 server. One overcurrent protective device is required for
each power supply line. The overcurrent protective devices must comply with the
following specifications:
■
Current rating: 30 A
■
Voltage rating: at least 65 Vdc
■
Operation type: Immediate shutdown type (however, overcurrent protective
devices should not operate against 1 ms rush currents with a peak current of
100 A)
■
Number of poles: 2 (-48 Vdc to -60 Vdc line and RTN line)
TABLE C-2
DC Power Cord Specifications
Item
Specification
Connector
294-0085-00100A of ELCON
Cable structure
Three AWG 14 wires
Cable length
5 m
FG
-48 Vdc to -60 Vdc (wire color: blue)
-48 Vdc to -60 Vdc
RTN
RTN (wire color: black)
FG (wire color: green and yellow)
Summary of Contents for Enterprise M3000
Page 4: ......
Page 8: ...viii SPARC Enterprise M3000 Server Installation Guide March 2012 ...
Page 34: ...3 14 SPARC Enterprise M3000 Server Installation Guide March 2012 ...
Page 42: ...4 8 SPARC Enterprise M3000 Server Installation Guide March 2012 ...
Page 60: ...B 10 SPARC Enterprise M3000 Server Installation Guide March 2012 ...