animeo KNX 4 AC MoCo · REF. 5071074 -
30/47
Basic function
Selection options:
Venetian blind UP / DOWN
Switch/Dry contact
8-Bit value (rising edge)
Dimming
Longer operation (dimming) after
Selection options:
0.5 seconds
0.3 - 0.5 seconds
This parameter defines the activity time of the corresponding push button which makes a distinction between the sending of a switching
telegram and a dimming telegram. If the time, for example, is parametered on
0.5 seconds,
a dimming telegram is generated only after a
press activation longer than 0.5 seconds is made. With a pressing shorter than
0.5 seconds
a switch telegram is generated.
Input A/B
Selection options:
On/Off
Toggle/Toggle
This parameter defines the value which is transmitted with a short pressing of the corresponding input.
On/Off
With a short pressing of the push button at the input A, an "Off" telegram is generated. With a short activity of the corresponding push
button at the input B, an "On" telegram is generated. This function can be inverted by changing over the clamps at the inputs.
Toggle/Toggle
Switching over can be done with a short pressing of the push button at the input A or B. This means that the value which is in the corre-
sponding switching object is firstly inverted and is then transmitted.
On ("1")
Off ("0")
Toggle ("1/0")
"Push button binary input 1 ... 4"