FG-200 HSE/FF Modbus - User Manual
74
Version EN-112021-1.30.3
9.4
Coding of bit fields
Parameter BLOCK_ERR
No error
0x0000
Out Of Service
0x0001
Power up
0x0002
Device needs maintenance
0x0004
Readback check failed
0x0008
Lost nv data
0x0010
Lost static data
0x0020
Memory failure
0x0040
Output failure
0x0080
Input failure
0x0100
Dev needs maint soon
0x0200
Dev fault state set
0x0400
Local override
0x0800
Simulate active
0x1000
Link config err
0x2000
Block config err
0x4000
Other
0x8000
Parameter MODE_BLK:
Out Of Service
0x01
Initialization Manual
0x02
Local Override
0x04
Manual
0x08
Auto
0x10
Cascade
0x20
Remote-Cascade
0x40
Remote-Output
0x80
Modbus Register 16 Bit register contains target mode in High Byte, actual mode in low byte.
Example: Modbus value 0x1001 means: target mode = Auto, actual mode = Out Of Service
Field Diagnostics (Parameter FD_FAIL, FD_OFFSPEC, FD_CHECK, FD_MAINT)
The bit fields are vendor specific and not specified by FIELDBUS Foundation except the least significant bit
(LSB). The LSB indicates the check function to be active. The check function is typically mapped to the
FD_CHECK parameter but may also be mapped to any of the other FD_xxx parameters.
The value for LSB is 0x80000000, the value for the most significant bit (MSB) is 0x00000001.
Summary of Contents for FG-200 HSE/FF
Page 1: ...Softing Industrial Automation GmbH FG 200 HSE FF Modbus User Manual Version EN 112021 1 30 3...
Page 49: ...Chapter 6 Using the web interface Version EN 112021 1 30 3 49...
Page 56: ...FG 200 HSE FF Modbus User Manual 56 Version EN 112021 1 30 3...
Page 77: ...Chapter 10 ATEX Type Examination Certificate Version EN 112021 1 30 3 77...
Page 78: ...FG 200 HSE FF Modbus User Manual 78 Version EN 112021 1 30 3...
Page 81: ...Chapter 12 Declarations of conformity Version EN 112021 1 30 3 81...