Chapter 8 - LED status indicators
Version EN-112021-1.30.3
59
8.3
Device LED statuses in redundant mode
The redundancy link LED is used to indicate if traffic via the serial line is performed. It will flash green if a
valid message is received. It will switch to red if serial communication is lost and it will be off if no serial
response has been received after startup.
flashing green
redundancy link communication is ok (triggered by redundancy link packets)
red
link communication interrupted or aborted (broken down)
off
no link communication at all
LEDs
Meaning
PWR
RUN
green
ERR
RDL
Start–up phase (approx. 7 seconds)
During this phase redundancy role is determined.
PWR
RUN
green
green
ERR
RDL
Non redundant device, ready.
The device is operational; it is not part of a redundant set.
Primary Device is redundant set.
The device is operational, acting as Primary Device in a
redundant set. The secondary device is ready
PWR
RUN
green
green
red
ERR
RDL
Permanent hardware fault detection during startup.
A fatal error has been detected. Possible failure could be a
missing Ethernet connection.
PWR
RUN
green
green
red
ERR
RDL
Primary device or non-redundant device, hardware failure.
The device is acting as non-redundant device, but a minor
hardware failure has been detected during start-up.
In the case of a Primary Device on a redundant set, the
secondary device is not ready
PWR
RUN
green
green
red
ERR
RDL
Primary device or non-redundant device, failure.
The device is acting as non-redundant device, but a failure has
been detected.
or
Secondary device, not ready.
The device is acting as secondary device in a redundant set,
but it is not ready to take over the primary role due to e.g. not
synchronized configuration information or a non-operational
redundancy link.
or
Primary Device or non-redundant device, failure.
Summary of Contents for FG-200 HSE/FF
Page 1: ...Softing Industrial Automation GmbH FG 200 HSE FF Modbus User Manual Version EN 112021 1 30 3...
Page 49: ...Chapter 6 Using the web interface Version EN 112021 1 30 3 49...
Page 56: ...FG 200 HSE FF Modbus User Manual 56 Version EN 112021 1 30 3...
Page 77: ...Chapter 10 ATEX Type Examination Certificate Version EN 112021 1 30 3 77...
Page 78: ...FG 200 HSE FF Modbus User Manual 78 Version EN 112021 1 30 3...
Page 81: ...Chapter 12 Declarations of conformity Version EN 112021 1 30 3 81...