Chapter 5 - Working with the FG-200 HSE/FF Modbus
Version EN-112021-1.30.3
29
5.2
FG-200 acts as a FF-HSE/ FF-H1 gateway
5.2.1
FG-200 acts as an H1 interface used by Emerson AMS System
Emerson provides its AMS Device Manager for calibration, diagnostics and device configuration for various
fieldbus technologies. Using the FG-200 enables AMS Device Manager to access FF-H1 devices. As a
precondition it is necessary to enable FF-HSE interface in the AMS Device Manager and integrate the FF
device descriptions of the FG-200 (CFH-File) and the H1 Devices that have to be accessed.
In order to use the FG-200 the following general settings have to be done via the webserver interface:
Make sure
Enable automatic VCR Creation
is activated. Otherwise no access to H1 device parameters
would be necessary.
Additional settings depend on the user scenario:
Offline access (Standalone network FG-200 and H1 devices)
In this scenario the FG-200 would be the primary host device and
Link Master Functionality
is activated. In
addition we recommend disabling the
Visitor Mode
and setting Node Address to 16 or 17. Make sure all
required H1 Links are activated i.e. a Link ID >= 0x1000 is assigned for those links.
Access in field (H1 devices are used as part of a control system)
For this scenario we recommend configuring the Node Address within the range from 252 to 255 for the
FG-200. If you want prevent the FG-200 to take an active role in the H1 segments, deactivate
Link Master
Functionality
. Usually this is not required if the H1 bus parameters used in the control system are not too
slow.
If
Link Master Functionality
is activated make sure that all activated H1 links of the FG-200 are connected
to H1 segments with an active host system interface. Otherwise the FG-200 would wait for a 6 minute
period for activity on the H1 segments and would then disable the segments without activity i.e. the
segments without an active host interface.
Summary of Contents for FG-200 HSE/FF
Page 1: ...Softing Industrial Automation GmbH FG 200 HSE FF Modbus User Manual Version EN 112021 1 30 3...
Page 49: ...Chapter 6 Using the web interface Version EN 112021 1 30 3 49...
Page 56: ...FG 200 HSE FF Modbus User Manual 56 Version EN 112021 1 30 3...
Page 77: ...Chapter 10 ATEX Type Examination Certificate Version EN 112021 1 30 3 77...
Page 78: ...FG 200 HSE FF Modbus User Manual 78 Version EN 112021 1 30 3...
Page 81: ...Chapter 12 Declarations of conformity Version EN 112021 1 30 3 81...