6.5.4.4 HSE
The HSE submenu allows to specify the
Alarm Distribution Address
and the
Alarm Distribution Port
. These
parameters are the Multicast Address and the UDP Port that are used by the FG-200 to forward alarms
from H1 devices.
Note
The default settings "Address = 239.255.0.33" and "Port = 45000" are required for
interoperability with Emerson AMS tool.
Changing these parameters may disable the display of alarm conditions in AMS alert
monitoring.
If a different HSE host tool is used, the parameter could be adapted to the values required by that tool.
Click
[Change Settings]
to apply your modifications.
6.5.5
Modbus
The FG-200 allows traditional control systems access to H1 fieldbus devices as well as over the serial port
RS485 and using TCP/IP. These control systems normally include support for the Modbus communication
protocol.
6.5.5.1 Communication
The Communication submenu allows to configure the Modbus Communication settings.
Hint
Before you modify settings make sure that the Modbus function is enabled and all parameters
are set to a valid value. Therefore consult the manual of your particular Modbus client and
adjust the Modbus configuration accordingly.
Most of the settings are self-explanatory and are related to configuring the serial port to match the
settings used by the Modbus Master.
If you are using Modbus TCP/IP over the Ethernet, then the communication settings (baud rate, parity, stop
bits) can be ignored.
Click
[Change Settings]
to apply your modifications.
Summary of Contents for FG-200 HSE/FF
Page 1: ...Softing Industrial Automation GmbH FG 200 HSE FF Modbus User Manual Version EN 112021 1 30 3...
Page 49: ...Chapter 6 Using the web interface Version EN 112021 1 30 3 49...
Page 56: ...FG 200 HSE FF Modbus User Manual 56 Version EN 112021 1 30 3...
Page 77: ...Chapter 10 ATEX Type Examination Certificate Version EN 112021 1 30 3 77...
Page 78: ...FG 200 HSE FF Modbus User Manual 78 Version EN 112021 1 30 3...
Page 81: ...Chapter 12 Declarations of conformity Version EN 112021 1 30 3 81...