FG-200 HSE/FF Modbus - User Manual
22
Version EN-112021-1.30.3
3.1.9
Connecting FF-H1 interfaces
Connect the H1 links to the terminal blocks of the H1 interfaces. Since the FG-200 does not provide power
to the H1 links, a power conditioner and a bus termination is required for each H1 link. When using a
redundant set of two devices, make sure to connect each H1 link to the same channel (CH 1 .. CH 4) on
both FG-200s.
The FG-200 provides four Foundation Fieldbus H1 interfaces. These interfaces are named CH1 to CH4 and
are used to connect an FF-H1 bus to the FG-200.
FF H1 bus line channel 1
CH1
Pin
Signal
Description
7
+
Fi
8
S
Fieldbus shield
9
-
Fieldbus -
FF H1 bus line channel 2
CH2
Pin
Signal
Description
10
+
Fi
11
S
Fieldbus shield
12
-
Fieldbus -
FF H1 bus line channel 3
CH3
Pin
Signal
Description
13
+
Fi
14
S
Fieldbus shield
15
-
Fieldbus -
FF H1 bus line channel 4
CH4
Pin
Signal
Description
16
+
Fi
17
S
Fieldbus shield
18
-
Fieldbus -
Note
The fieldbus shield is not connected directly to functional earth. For EMC reasons, it is only
connected via a capacitor. If a direct connection to functional earth or protective earth is
required, you need to implement this separately.
Summary of Contents for FG-200 HSE/FF
Page 1: ...Softing Industrial Automation GmbH FG 200 HSE FF Modbus User Manual Version EN 112021 1 30 3...
Page 49: ...Chapter 6 Using the web interface Version EN 112021 1 30 3 49...
Page 56: ...FG 200 HSE FF Modbus User Manual 56 Version EN 112021 1 30 3...
Page 77: ...Chapter 10 ATEX Type Examination Certificate Version EN 112021 1 30 3 77...
Page 78: ...FG 200 HSE FF Modbus User Manual 78 Version EN 112021 1 30 3...
Page 81: ...Chapter 12 Declarations of conformity Version EN 112021 1 30 3 81...