FG-200 HSE/FF Modbus - User Manual
30
Version EN-112021-1.30.3
H1 Device Alarms
AMS Device Manager supports monitoring a subset of H1 device alarms. To make use of this functionality
you need to enable this feature in the AMS Device Manager and to configure the FG-200 and the attached
H1 devices accordingly. Note that within AMS Device Manager alarms are designated as "Alerts". Activate
this setting with
Enable HSE Alarms
in the General Settings web page of the FG-200.
We recommend activating
Visitor Mode
in the
General settings
web page. Thus you disable the alarm
configuration of H1 devices. This would prevent an impact on an existing device configuration but could
lead to situations where it is not possible to receive alarms from some H1 devices. To display which
devices are affected go to
Configuration
à
Fieldbus
à
Device
and search in column "Alarm configured"
for the respective device.
AMS Device Manager is supporting standard Fieldbus Foundation alarm messaging using the UDP protocol,
but it has an preconfigured UDP multicast address (239.255.0.33) and UDP port (45000) for the reception
of the alarm messages. This is used as default in the FG-200 but could be altered if a future AMS Device
Manager version would expect a different multicast address or UDP port by changing the settings in the
following web page.
Summary of Contents for FG-200 HSE/FF
Page 1: ...Softing Industrial Automation GmbH FG 200 HSE FF Modbus User Manual Version EN 112021 1 30 3...
Page 49: ...Chapter 6 Using the web interface Version EN 112021 1 30 3 49...
Page 56: ...FG 200 HSE FF Modbus User Manual 56 Version EN 112021 1 30 3...
Page 77: ...Chapter 10 ATEX Type Examination Certificate Version EN 112021 1 30 3 77...
Page 78: ...FG 200 HSE FF Modbus User Manual 78 Version EN 112021 1 30 3...
Page 81: ...Chapter 12 Declarations of conformity Version EN 112021 1 30 3 81...