Chapter 3 - Installation
Version EN-112021-1.30.3
13
Pair of values for fieldbus voltage and current for Intrinsic Safety Fieldbus (ic):
Pair 1
Pair 2
Pair 3
Fieldbus Voltage
Ui = 14 Volt DC
Ui = 17.5 Volt DC
Ui = 32 Volt DC
Fieldbus Current
li = 570 mA
li = 319 mA
li = 100 mA
CAUTION
Make sure that the sum of power supply voltage and fieldbus supply voltage does not exceed
60 VDC!
Explosion hazard
Do not disconnect equipment unless power has been removed or the area is known to be
non-hazardous.
Observe relevant national regulations, standards and directives
This manual does not supersede the relevant national regulations, standards and directives.
These must be observed and have to be applied according to the national conditions!
3.1.1.2 Hazardous Location - European and International Approval (ATEX, IECEx)
The equipment has been assessed as based on the following standards and editions:
a) EN IEC 60079-0:2018
b) IEC 60079-11:2011 Ed. 6 + Corr. 2012 / EN 60079-11:2012
c) EN IEC 60079-7:2015+A1:2018
If indicated on the device label or by technical documentation, the FG-200 is suitable for use in gas-Ex
atmospheres of Zone 2 in the explosion groups IIA, IIB and IIC in temperature class T4, if accommodated in
a tested enclosure.
§
IECEx BVS 15.0055 x marking for explosion protection: Ex ec IIC T4 Gc,
Ex ec [ic] IIC T4 Gc
§
BVS 15 ATEX E 063 X marking for explosion protection: II 3G
The Ex protection method [ic] corresponds only to the FF-H1 fieldbus interfaces.
The FG-200 HSE/FF Modbus complies with the applicable standards and regulations and meets the
requirements of Directive 2014/35/EU. The requirements for erecting the device as part of the system in
potentially explosive atmospheres (e.g. IEC / EN 60079-14) must be strictly adhered.
Summary of Contents for FG-200 HSE/FF
Page 1: ...Softing Industrial Automation GmbH FG 200 HSE FF Modbus User Manual Version EN 112021 1 30 3...
Page 49: ...Chapter 6 Using the web interface Version EN 112021 1 30 3 49...
Page 56: ...FG 200 HSE FF Modbus User Manual 56 Version EN 112021 1 30 3...
Page 77: ...Chapter 10 ATEX Type Examination Certificate Version EN 112021 1 30 3 77...
Page 78: ...FG 200 HSE FF Modbus User Manual 78 Version EN 112021 1 30 3...
Page 81: ...Chapter 12 Declarations of conformity Version EN 112021 1 30 3 81...