7. Trouble shooting and
maintenance
7.1. Trouble shooting
This section contains information and procedures for solving possible
problems with the SOFAR 3.3K~12KTL-X inverter.
In case of problem with inverter, check the following tips.
Check the warning fault messages or Fault codes on the inverter
information panel. Record it before doing anything further.
If inverter does not display any Fault, please check the following lists.
-Is the inverter located in a clean, dry, adequately ventilated place?
-Is the DC switch turned ON?
-Are the cables adequately sized and short enough?
-Are the input and output connections and wiring in good condition?
-Are the configuration settings correct for the particular installation?
-Are the display panel and the communications cable properly connected
and undamaged?
Follow the steps below to view recorded problems:
Press “ESC” to enter the main menu in the normal interface. In the
interface screen select “Event List”, then press “OK” to enter events.
Event List information
Table 7-1 Event list
Event List
NO.
Event List
Name
Event List
description
solution
ID01
GridOVP
The power grid
voltage is too
high
If the alarm occurs occasionally, the possible cause is that
the electric grid is abnormal occasionally. SOFAR inverter
automatically returns to normal operating status when the
electric grid’s back to normal.
If the alarm occurs frequently, check whether the grid
voltage/frequency is within the acceptable range. If no,
contact SOFAR technical support. If yes, check the AC
circuit breaker and AC wiring of the SOFAR inverter.
If the grid voltage/frequency is within the acceptable range
ID02
GridUVP
The power grid
voltage is too
low
ID03
GridOFP
The power grid
frequency is
too high