SOFAR 3.3K~12KTL-X
User manual
All rights reserved
©
Shenzhen SOFARSOLAR Co ., Ltd.
- 18 -
Figure4-2 Ground terminal composition
4.3. Connecting AC Output Power Cables
Connect the SOFAR 3.3K~12KTL-X to the AC power distribution frame
(PDF) or electrical grid using AC output power cables.
It is not allowed for several inverters to use the same circuit breaker.
It is not allowed to connect loads between inverter and circuit breaker.
Caution
Context
All the AC output cables used for the inverters are outdoor five-core cables.
To facilitate the installation, use flexible cables . Table 4-1 lists the
recommended specifications for the cables and the breakers.
Table4-1
The models marked with“ *” should be available only for some designated
countries.
Note: For the sake of safety, please make sure to use correctly sized cables,
otherwise the current makes the cable overheat or overload, even cause a fire.
Type
Sofar *
3.3
KTL-X
Sofar
4.4
KTL-X
Sofar *
5
KTL-X
(Australia)
Sofar
5.5
KTL-X
Sofar
6.6
KTL-X
Sofar
8.8
KTL-X
Sofar
11
KTL-X
Sofar
12
KTL-X
Cable(Copper) 4-6mm
2
4-6mm
2
4-6mm
2
4-6mm
2
4-6mm
2
4-6mm
2
4-6mm
2
4-6mm
2
Breaker
10A
10A
10A
10A
16A
16A
20A
25A