23
Grid Type
<Medium Voltage
>
Grid Parameter
<Customization>
Regulation Parameter
VH L1 : 276.0 0.50s
VL L1 : 184.0 1.00s
VH L2 : 276.0 0.50s
VH L1 : 184.0 1.00s
FH L1 : 52.0Hz 1.50s
FL L1 : 47.0Hz 5.00s
FH L2 : 52.0Hz 1.50s
After that choose the grid type:
1.
Low voltage: the delivery of the energy of the system is in low voltage
2.
Medium voltage: delivery of the energy of the system is in medium voltage
Then is necessary to set the inverter parameters:
1.
Default: the parameters are the default parameter specified in the regulatory of the contry selected
2.
Customization: All parameters are settable in accordance with the regulatory of the country selected
if it is set "cusomization" in subsequent windows will be set one by one all the parameters.
For accept press "OK".
At the end of all setting there is a summary window.
Press the “
↓
” arrow to scroll all parameter.
Grid High Voltage
Level 1
<276.0>
Grid Parameter
<Default>
Grid Type
<Low Voltage>
Green backlight
Green backlight