31
Password
: Select char
: Delete : Next
7.
Regulation parameter
By pressing
“
↓
” again on the “System Information”, the LCD changes to “Regulation Parameter” as shown
below. The LCD displays all the inverter parameters that have been stetted at initial setup.
By pressin
g “
→
” is possible to scroll all the parameters.
As long
you remain on this screen is possible, by pressing the “OK” keys for 10 seconds and by insert a
password “4613”, to set all parameters again.
See “Grid Parameter” settings at point 6.1 for more details.
8.
Reactive power function
When is pressed
“
↓
” again appears the “Reactive Power Function” screen.
By pressing the “OK” keys for 10 seconds and by insert a password “4613”, is possible to choose a method of
managing the reactive power, or if it is already active, is possible to disable it.
Password
: Select char
: Delete : Next
Regulation Parameter
VH L1 : 276.0V 0.50s
VL L1 : 184.0V 1.00s
VH L2 : 184.0V 0.50s
VH L2 : 184.0V 1.00s
Power Reduction : 2.4%
Reactive Power Func.
Mode : Off
Value : N/A
Press OK over 10s to
Change the setting