Example of configuring an alarm on a digital input via Easy Config:
13 .1 .7 . Preconfigured load management alarms (only available with DIRIS Digiware S-Datacenter)
DIRIS Digiware S-Datacenter has 9 preconfigured alarms, alerting the user of the load level on each current input:
• Full load: when the load level reaches 80% of the nominal current.
• High load: when the load level reaches 60% of the nominal current.
• No load: when the load level drops to 0% of the nominal current.
The nominal current is 32A by default. It can be changed from the “Loads” configuration menu of the DIRIS
Digiware S module in Easy Config or from the DIRIS Digiware D-xx display.
13.2. combination of alarms
• 4 boolean combinations (OR, AND) on the defined alarms (electrical values, energy, inputs, etc.)
Example of configuring an alarm on a digital input via Easy Config: