22
EN
DIRIS DIGIWARE - 546420C - SOCOMEC
6.2. connecting to the electrical network and loads
The DIRIS Digiware U-xx modules can be used on single-phase, two-phase or three-phase electrical networks.
Each DIRIS Digiware S-xx current sensing module can use its three current inputs to simultaneously measure
several loads, for example three single-phase loads.
In addition, within one DIRIS Digiware system, different load types may be measured. For example, several Digiware
S-xx modules may be configured as single-phase loads while others may be configured to measure three-phase
loads.
This approach allows great flexibility within the electrical installation which may contain several different load types.
6 .2 .1 . Configurable loads based on the network type
The following table summarises the loads which can be configured based on the installation's network type
Network type
Configurable load
1P+n
1P+N – 1CT
2P
2P – 1CT
2P+n
2P+N – 2CT / 2P – 1CT / 1P+N – 1CT
3P*
3P – 3CT / 3P – 2CT / 3P – 1CT
3P+N
3P+N – 3CT / 3P+N – 1CT / 3P – 3CT / 3P – 2CT / 3P – 1CT / 1P+N – 1CT
(*) Note: Single-phase loads cannot exist on a 3P network.
6 .2 .2 . Description of the main network and load combinations
legend:
3P+n – 3ct
I01
I02
I03
I01
I02
I03
I01
I02
I03
I01
I02
I03
I01
I02
I03
I01
I02
I03
V1 V2 V3 VN
V
L1
L2
L3
N
V1 V2 V3 VN
V
L1
L2
L3
N
V1 V2 V3 VN
V
L1
L2
N
V1 V2 V3 VN
V
L1
L2
L3
N
3
3
V1 V2 V3 VN
V
L1
N
V1 V2 V3 VN
V
L1
L2
N
1
1
1
1
1
1
1
1
1
2
2
Three phase load
DIRIS Digiware S
Voltage terminal
Three phase + Neutral
network with 3 current
sensors
I01
I02
I03
DIRIS Digiware S
current inputs
I01, I02, I03
3
3
Three phase load