53
EN
DIRIS DIGIWARE - 546420C - SOCOMEC
current sensing - Diris Digiware s
Number of current inputs
3
Accuracy of current measurement
Class 0.5
Basic current Ib
Maximum current Imax
10 A
63 A
Link with DIRIS Digiware U voltage module
The first DIRIS Digiware S current sensing module is linked to the
DIRIS Digiware U voltage module by a Digiware Bus
Link with DIRIS Digiware S current module
The DIRIS Digiware S current modules are interconnected by the
Digiware Bus with bus termination for the last module
Digital inputs/outputs- Diris Digiware io-10
Number of inputs
4
Type / Power supply
Insulated input, internal polarisation 12 VDC max., 3 mA - SELV
Input functions
Logical status
State of the circuit breaker: position, trip status, drawer status
Pulse counter: choice of pulse weight, measurement unit, tariff rates (max. 8)
Connection
Removable screw terminal block, 9 positions - 5 dedicated to inputs,
stranded or solid 0.14 - 1.5 mm² cable
Number of outputs
2
Type
Insulated output, 48 VDC max., 50 mA and 24 VAC max. - SELV
Output functions
Configurable alarm on threshold overruns
Remote control of devices
Connection
Removable screw terminal block, 9 positions - 4 dedicated to outputs,
stranded or solid 0.14 - 1.5 mm² cable
analog inputs - Diris Digiware io-20
Number of inputs
2
Type / Power supply
0/4-20mA, 200 Ω max - SELV
Accuracy
0.5% full scale
Function
Connection of analogue sensors (pressure, humidity, temperature...) with
linear or quadratic interpolation
Connection
Removable screw terminal block, 2x2 positions, stranded or solid
0.14 - 1.5 mm² cable
14 .1 .6 . Communication characteristics
Digiware bus
Function
Connection between DIRIS Digiware modules
Cable type
Specific SOCOMEC cable with RJ45 connections
rs485
Connection type
2 - 3 half duplex wires
Protocol
Modbus RTU
Baudrate
9600 to 115 200 bauds
Function
Configuration and reading of centralised data on the DIRIS Digiware U
and all of the DIRIS Digiware I linked by the Digiware bus
Location
Single-point on DIRIS Digiware C
Connection
Removable screw terminal block, 3 positions, stranded or solid
0.14 - 1.5 mm² cable
usb
Protocol
Modbus RTU on USB
Function
Configuration of DIRIS Digiware U and I modules
Location
On each DIRIS Digiware U and I measurement module
Connection
Type B micro USB connector