30
EN
DIRIS DIGIWARE - 546420C - SOCOMEC
• Diris Digiware s-xx:
main leD
Fixed
blinking
green
Product in normal operation
Product in communication
and
During 10 seconds, if an identification request is
initiated from the Easy Config software
red
Indicates the presence of a measurement alarm
(does not have priority over system alarms)
Indicates the presence of a system alarm (**)
orange
Address conflict during an auto detection process
initiated from a D-xx display or a G-xx gateway
Not available
i01, i02 & i03
leDs (***)
Fixed
Pulse
red
Indicates that no voltage is detected on a phase.
Corresponds to the metrological pulse weight
(1Wh by default)
(**) System alarms for the DIRIS Digiware S module can be a bad V/I association indicating a possible wiring error.
(***) By default, I01, I02, I03 LEDs are configured in voltage detection mode.
Settings can be changed to metrological LED mode from the Easy Config configuration software.
The voltage detection feature is an indication of the presence or the absence of voltage on one of the
phases. It should only be used as an indication, and must not replace the use of a voltage tester.
In addition, the nominal voltage must be correctly configured in the DIRIS Digiware U module
8.2. auto-addressing
With the auto-addressing mode you can have the system automatically assign addresses to devices connected to
the DIRIS G gateways or DIRIS Digiware D remote displays. This mode is only compatible with DIRIS B-30 , DIRIS
A-40 and DIRIS Digiware PMDs. The addresses will need to be allocated manually on the other PMD (DIRIS A) and
meters (COUNTIS).
Two modes are available:
• Mode 1 - Auto-detection and automatic addressing
• Mode 2 - Auto-detection and address selection
Mode 1 is without external equipment (see description below).
Mode 2 is carried out from a PC equipped with Easy Config.