44
EN
DIRIS DIGIWARE - 546420C - SOCOMEC
12. autocorrect tecHnology: automatic
Detection anD correction oF wiring errors
The AutoCorrect technology enables a detection and possible software correction of wiring errors such as a phase
inversion on the current inputs of the DIRIS Digiware S module. This is illustrated in the example below:
L1
L2
L3
• Changing phase association using the device’s front button
Pressing the front button of the DIRIS Digiware S module for 5s will automatically correct the wiring and inform you with an LED
sequence of the physical connection between the device’s current inputs and the network lines.
After launching AutoCorrect from the device’s push-button, the I01, I02 and I03 LEDs will blink with the specific sequence:
One blink means the current input is associated to the network line 1,
Two blinks means the current input is associated to the network line 2,
Three blinks means the current input is associated to network line 3.
Ex: After pressing the device’s push-button for 5s, the following LED sequence is given:
current, input
blink
I01, I02, I03
Blink once simultaneously indicating the start of the AutoCorrect process
I01
Three times
I02
Twice
I03
Once
I01, I02, I03
Blink once simultaneously indicating the end of the AutoCorrect process
This sequence indicates that:
Current input I01 is associated to Network line 3
Current input I02 is associated to Network line 2
Current input I03 is associated to Network line 1