25
EN
DIRIS DIGIWARE - 546420C - SOCOMEC
7. Digiware bus
7.1. Principle
or
u module
DIRIS Digiware U-xx
system interface
module
DIRIS Digiware C-31
Display
DIRIS
Digiware D-xx
current sensing
module
DIRIS Digiware S-xx
Input/Output module
DIRIS Digiware IO-xx
Digiware Bus
Termination
Digiware Bus
DIRIS Digiware is a system comprising the following elements:
• One DIRIS Digiware D remote display or one DIRIS Digiware C-31 system interface module
• A DIRIS Digiware U voltage measurement module
• One or multiple DIRIS Digiware S current sensing modules
• One or multiple DIRIS Digiware IO input/output modules
• A Digiware bus termination (ref. 4829 0180) positioned on the last module. It is provided with the DIRIS Digiware
D display and the DIRIS Digiware C-31 system interface module.
Note: For the measurement of circuits with a higher current rating, DIRIS Digiware I-xx current measurement
modules associated with TE, TR/iTR or TF current sensors can be used, making the DIRIS Digiware system suitable
for all levels within the electrical installation (MAIN, subfeed, terminal circuits...)
7 .1 .1 . Digiware Bus connection cables
Length (m)
Quantity
Part number
0.06
1
4829 0189
0.1
1
4829 0181
0.2
1
4829 0188
0.5
1
4829 0182
1
1
4829 0183
2
1
4829 0184
5
1
4829 0186
10
1
4829 0187
50-m reel + 100 connectors
4829 0185
Use the shortest possible cables to optimise the electromagnetic emissions.
The total max. length must not exceed 100 metres.