9 .2 .3 . Connection with the DIRIS Digiware D-40 remote display
In an RS485 link, a DIRIS Digiware D-40 remote display is a slave device of the RS485 bus and links to the DIRIS
Digiware bus.
The following rules must be observed:
• A 120 Ω resistor must be added at the start of the RS485 link
• A 120 Ω resistor must be added at the end of the RS485 link
• A termination must be added at the end of the Digiware bus.
Connection example:
Bus Digiware
Termination
DIRIS Digiware D-40
PC
RS485
DIRIS Digiware U
DIRIS Digiware S
Digiware Bus
120 Ω
120 Ω
You can show up to 32 devices on the DIRIS Digiware D-40 display.
9.3. communication tables
The full communication tables for each module can be found on
the SOCOMEC website at the following address:
www.socomec.com/en/diris-digiware
The communication tables are sent via JBUS (Modbus).