52
EN
DIRIS DIGIWARE - 546420C - SOCOMEC
Frequency accuracy
Class 0.02
Network type
Single-phase/ Two-phase / Two-phase with neutral / Three-phase / Three-
phase with neutral
Measurement by voltage transformer
Primary: 400,000 VAC
Secondary: 60, 100, 110, 173, 190 VAC
Input consumption
≤ 0.1 VA
Rated impulse voltage
IEC 60947-1 V. IMP: 6.4 kV
Accuracy of voltage measurement
Class 0.2
Connection
Removable screw terminal block, 4 positions, stranded or solid 0.2 -
2.5 mm² cable
Link with DIRIS Digiware S current sensing
module
The first DIRIS Digiware S current sensing module is linked to the
DIRIS Digiware U voltage module by a Digiware Bus