DIRIS DIGIWARE - 546420C - SOCOMEC
6. connection
6.1. Diris Digiware s connection
Use
rJ45 Digiware bus cables
(UTP RJ45 straight, twisted pairs, unshielded, AWG24, 600V, Cat 5
rated, -10 / +70 °C) between all DIRIS Digiware modules.
Do not put single insulated cables or active parts near the micro-USB or Digiware RJ45 port of the device.
Do not pull on the RJ45 cable more than 20N.
Display
Diris Digiware D
Diris
Digiware s
l1
l1
l2
l2
l3
l3
Digiware bus
termination
Diris
Digiwar
e U
Voltage
Inputs (U)
Diris
Digiwar
e C
Supply
& Com
Digiware
bus
communication
rs485 modbus selV
7 mm
solid 0.14 mm
2
-> 1.5 mm
2
stranded 0.14 mm
2
-> 1.5 mm
2
3 positions - screw 0.25 Nm max.
24VDc selV
7 mm
solid 0.2 mm
2
-> 2.5 mm
2
stranded 0.2 mm
2
-> 2.5 mm
2
2 positions - screw 0.25 Nm max.
u
Voltage inputs
50-300Vac PH/n
7 mm
solid 0.2 mm
2
-> 2.5 mm
2
stranded 0.2 mm
2
-> 2.5 mm
2
4 positions
screw 0.25 Nm max.
L1
L2
L3
N
Micro
USB
type B
or
supply
(*)
rs485 line Polarisation
OFF = RS485 Line
Polarisation disabled
(by default)
ON = RS485 Line
Polarisation enabled
24 V
SUPPL
Y
RS485
NC
1
2
ON
The Device must be fitted on insulated
cables only:
300V or 600V insulation depending on the
voltage level of the electrical installation.
SELV: Safety Extra Low Voltage
(*) Earth should not be wired in unearthed systems