78600-01NM Fire Alarm Repeat Panel Set
78600-82NM Fire Alarm Repeat Panel
Where appropriate refer to as fitted wiring diagrams (if supplied), general notes,
EMC compliance, LVD Compliance, cable types and loop circuit connections.
Fuses and locations
Fuse
Rating
Location
Mains
20mm x 5mm 1A SD
Mains terminal block
FS1
20mm x 5mm 2.5A QB
MRC pcb
FS2
20mm x 5mm 2.5A QB
MRC pcb
The repeat panel can be surface or flush mounted.
a)
Identify the FIRE ALARM REPEAT PANEL package and check the
contents, which should include:
Component
Quantity
Repeat panel
1
Fuse 1A
1
Fuse 2.5A
1
Door key
1
Enable controls key
1
CAUTION: 2off 12V @ 7.0Ah Sealed Lead Acid batteries must
be used for the repeat panel.
b)
Open the panel door using the door key.
c)
Remove the backbox to door earth lead.
d)
Disconnect the two ribbon cables from the main controller board,
mounted on inside of door.
e)
Remove the door.
f)
Remove the back box to cover earth lead.
g)
Loosen the cover captive screw and then remove the cover.
h)
Knockout the required cable entry points from the back box.
i)
If the panel is to be flush mounted then follow the instructions for
flush mounting the repeat panel now.
j)
Mark out the 3 back box fixing points on the wall to which the panel
is to be mounted.
78600-01NM Fire Alarm Repeat Panel Set
Standalone System Installation
Senator II Installation Manual
6-8
78910-03NM Issue 2_10/96