Standalone System Installation
78500-02NM Fire Alarm Control Panel Set
The 78500-02NM Control Panel Set consists of two (or more) packages:
78500-82NM Fire Alarm Control Panel
78510-02NM Battery Unit
78534-82NM Power Supply Unit and/or 1-5 Cards (see supplier for de-
tails)
78500-82NM Fire Alarm Control Panel
Where appropriate refer to as fitted wiring diagrams (if supplied), general notes,
EMC compliance, LVD Compliance, cable types and loop circuit connections.
Fuses and locations
Fuse
Rating
Location
Mains
20mm x 5mm 3.15A SD
Mains terminal block
FS1
20mm x 5mm 1A HRC#
Master alarm terminal board
FS2
20mm x 5mm 1A HRC#
Master alarm terminal board
FS1
20mm x 5mm 8A QB
Power supply pcb
FS2
20mm x 5mm 8A QB
Power supply pcb
FS3
Not fitted
FS4
Not fitted
FS5
20mm x 5mm 8A QB
Power supply pcb
FS6
20mm x 5mm 8A QB
Power supply pcb
# - Master Alarm fuses
The control panel can be surface or flush mounted. If however the battery
Unit is to be close fitted beneath the control panel then the two can only be
surface mounted.
CAUTION: 4off 12V @ 12.0Ah Sealed Lead Acid batteries
must be used for the control panel.
NOTE: The battery box can accomodate up to 8 batteries to allow for
additional standby time.
Standalone System Installation
78500-02NM Fire Alarm Control Panel Set
78910-03NM Issue 2_10/96
6-1
Senator II Installation Manual