.78510-02NM Battery Unit
Fuses and locations
Fuse
Rating
Location
Batt1
20mm x 5mm 8A
Battery fuse board
Batt2
20mm x 5mm 8A
Battery fuse board
The battery Unit may be close fitted beneath the control panel using
standard conduit fittings (not supplied).
To maintain earth continuity an earth lead (not supplied) is required to be
connected between to an earth point in the control panel and battery Unit.
NOTE: The coupling length must not be less than 72mm.
Cable and
Distance
The recommended cable type is MICC. The following maximum cable
lengths must not be exceeded:
MICC 1.5mm
2
10m max.
MICC 2.5mm
2
15m max.
cdn4
Figure 6-4 Close fitting the Panel and Battery Unit
Standalone System Installation
.78510-02NM Battery Unit
78910-03NM Issue 2_10/96
6-5