a)
Identify the package labelled BATTERY UNIT and check the
contents, which should include:
Component
Quantity
Battery Unit
1
Door key
1
Fuse 8A (Battery)
2
Battery cable loom
2
Battery link
4
Nut and washer (for earth stud)
1
b)
Open the battery unit door using the door key.
c)
Remove the back box to door earth lead.
d)
Remove the door from the back box assembly, by sliding it up and
off.
e)
Knock out/in the appropriate cable entries. Mark out the back box
fixing points on the wall to which the box is to be mounted.
f)
Secure the back box to the wall with suitable fixings to provide
adequate support for a full assembly weight of 40kg, (with all 8
batteries installed).
CAUTION: Do not make the battery connections. This is done
during commissioning stage.
g)
Slide the door on to the back box assembly, ensure the door can open
and close easily.
h)
Fit the door to back box earth lead.
i)
Close the door and lock it using the door key.
j)
Continue with the control panel installation, if the battery Unit has
been close fitted to the control panel.
k)
All remaining installation is done during the commissioning of the
system.
CAUTION: 4off 12V @ 12.0Ah Sealed Lead Acid batteries
must be used for the control panel.
NOTE: The battery box can accomodate a maximum of 8 batteries if
required.
Fuses and locations
Standalone System Installation
Senator II Installation Manual
6-6
78910-03NM Issue 2_10/96