HRX-OM- T002
Chapter 3 Transport and Setting Up
HRS090 Series
3.2
Installation
3-7
Required facility water system
Table 3-3 Heat radiation
Model
Heat
radiation kW
Facility water specifications
HRS090-W
-20/40
Approx. 17
Refer to [9.1 Specifications].
Installation environment specification
Sound noise: HRS090-A-
: 73dB (A)
HRS090-A-40*:75
dB (A)
HRS090-W-
:
65dB (A)
Front 1m, height 1m, rated condition
The water cooled product radiates heat to the facility water.
It is necessary to supply the facility water. Please prepare the facility
water system that satisfies the heat radiation and the facility water
specifications below.