HRX-OM- T002
Chapter 5 Display and setting of various functions
5.5
Check monitor menu
HRS090 Series
5-12
Checking: Accumulated operating time of the compressor
9.
Press the [SEL] key once.
Display of the accumulated operating time of the compressor appears on the digital
display.
PV
SV
Refer to
” for the display.
AL30 Compressor maintenance alarm is generated when the accumulated operating
time of the compressor reaches 30,000 hours (
) (when set to
“A.RUN”). For
more details, refer to
Alarm Notification and Troubleshooting
”.
Checking: Accumulated operating time of the thermo-chiller
10.
Press the [SEL] key once.
The accumulated operating time of the thermo-chiller appears on the digital display.
PV
SV
Refer to “
” for the display.
Checking: Accumulated operating time of the dust-proof filter
11.
Press the [SEL] key once.
Display of the accumulated operating time of the dust-proof filter appears on the
digital display.
PV
SV
Refer to “
” for the display.
AL40 Dust-proof filter maintenance alarm is generated when the accumulated
operating time of the dust-proof filter reaches 500 hours (
) (when set to
“A.RUN”). For more details, refer to “Chapter 7
”.
Checking: Circulating fluid flow rate
12.
Press the [SEL] key once.
Display of the circulating fluid flow rate appears on the digital display.
PV
SV
Circulating fluid flow rate of this product is displayed as a guide. Unit: L/min.
This is not a measured value, and is provided as a guide.