HRX-OM- T002
Chapter 5 Display and setting of various functions
HRS090 Series
5.5
Check monitor menu
5-9
5.5 Check monitor menu
5.5.1
Check monitor menu
As a part of the daily inspection, the temperature, pressure and accumulated
operating time can be checked.
Please use this for confirmation of your daily inspection.
5.5.2
Checking with the Inspection monitor menu
The table below explains the check items of the inspection monitor menu.
Table 5.5-1
Check items in the check monitor menu
Display
Item
Content
Circulating fluid
discharge temperature
Displays the circulating fluid discharge temperature.
Offset temperature is not taken into consideration in
this temperature.
Circulating fluid inlet heat
exchanger temperature
Displays the circulating fluid temperature at the heat
exchanger inlet.
Compressor inlet temperature
Displays the refrigerant temperature at the compressor
inlet port.
Circulating fluid discharge pressure
Displays the circulating fluid discharg
e
pressure.
Refrigerant circuit pressure on the
high pressure side
Displays the pressure on the higher pressure side of the
refrigerant circuit.
Refrigerant circuit pressure
on the
low pressure side
Displays the pressure on the lower pressure side of the
refrigerant circuit.
Unused
-
Accumulated operating time of the
pump
Displays the accumulated operating time of the pump.
Accumulated operating time of the
fan
Displays the accumulated operating time of the fan
motor. (For air cooled type only)
Accumulated operating time of the
compressor
Displays the accumulated operating time of the
compressor.
Accumulated operating time of the
thermo-chiller
Displays the accumulated operating time of the
thermo-chiller.
Accumulated operating time of the
dust-proof filter
Displays the accumulated operating time of the
dust-proof filter.
Circulating fluid flow rate
Displays the circulating fluid flow rate. This is not a
measured value with a flow meter, and is provided as a
guide.
Checking: Circulating fluid discharge temperature
1.
Press and hold the [MENU] button for approximately 2 seconds.
Circulating fluid discharge temperature display
”
” appears on the digital display.
PV
SV
PV
SV
Displays the circulating fluid temperature discharged from this product to the user's
equipment. Offset temperature is not taken into consideration in this temperature.
Press and
hold
[MENU]
key