HRX-OM- T002
Chapter 5 Display and setting of various functions
5.19
Alarm customizing function
HRS090 Series
5-54
Setting/Checking: Threshold pressure setting for "Circulating fluid discharge pressure rise" alarm
14.
Press the [SEL] key once.
Threshold detecting pressure setting screen for "Circulating fluid discharge pressure
rise" alarm generation appears on the digital display.
PV
SV
15.
Set the threshold detection pressure for "Circulating fluid discharge pressure rise" alarm
generation with [▲] key or [▼] key, and press [SEL] key to enter.
Table 5.19-14 Threshold detecting pressure setting for "Circulating fluid discharge pressure rise" alarm
Set value
Explanation
Initial value
(Default setting)
Setting/checking of the alarm is impossible
when the "Circulating fluid discharge
pressure rise" alarm is set OFF.
MPa
Sets threshold detection pressure
for
”Circulating fluid discharge pressure
rise” alarm generation.
Pressure setting unit for MPa: 0.01 MPa
Pressure setting unit for PSI: 1 PSI
to
PSI
to
Setting/Checking: Operation setting when "Circulating fluid discharge pressure drop" alarm is generated
16.
Press the [SEL] key once.
Operation setting screen when "Circulating fluid discharge pressure drop" alarm is
generated appears on the digital display.
PV
SV