HRX-OM- T002
Chapter 5 Display and setting of various functions
HRS090 Series
5.19
Alarm customizing function
5-59
Setting/Checking: Monitoring start timer
32.
Press the [SEL] key once.
Setting screen of the monitoring start timer is displayed on the digital display.
PV
SV
33.
Set monitoring start timer with the [
▲] key or the [▼] key, and press [SEL] key to enter.
Table
5.19-23 Setting of the monitoring start timer
Set value
Explanation
Initial value
(Default setting)
Setting and checking are impossible when "0:
Continuous monitoring" or "1: Automatic
monitoring" is selected for the setting of AS21
"Temperature alarm monitoring method".
to
Sets the time when alarm monitoring starts.
Setting unit is 1 minute.
Settings of this function and example of alarm generating timing for
temperature alarm monitoring method and alarm generation timing
Setting/Checking: Range over detection timer
34.
Press the [SEL] key once.
Setting screen of the range over detection timer is displayed on the digital display.
PV
SV
35.
Set range over detection timer with the [
▲
] key or [
▼
] key, and press [SEL] key to
enter.
Table
5.19-24 Setting of the range over detection timer
Set value
Explanation
Initial value
(Default setting)
to
Sets time before the alarm is generated after
the alarm is generated.
Setting unit: 1 second
Settings of this function and example of alarm generating timing for
temperature alarm monitoring method and alarm generation timing