HRX-OM- T002
Chapter 7 Alarm Notification and Troubleshooting
7.3
Troubleshooting
HRS090 Series
7-10
7.3.3
How to release the pump thermal trip
1.
Shut of the breaker of the customer
’s power supply facility.
2.
Remove 12 screws to remove the upper panel.
Fig. 7-4
Removal of upper panel
3.
Remove 15 screws to remove the Left side panel.
Fig. 7-5 Removal of Left side panel
Be sure to lock out and tag out the breaker of the facility power supply
(customer power supply facility) before wiring.
Screw
Upper panel
Screw
Left side panel