HRX-OM- T002
Chapter 5 Display and setting of various functions
5.19
Alarm customizing function
HRS090 Series
5-50
Table 5.19-7 Default settings of the alarm customizing function (3/3)
Display
Content
Object alarm
Change content
Initial
setting
Code
Alarm name
Operation setting when
"Circulating fluid
discharge pressure
sensor error" alarm is
generated
AL25
Circulating fluid
discharge pressure
sensor failure
Product operation
while the alarm is
being generated
A.STP
Operation setting
during maintenance of
the pump
AL28
Pump maintenance
Product operation
while the alarm is
being generated
OFF
Operation setting
during maintenance of
the fan
AL29
*3
Fan maintenance
Alarm operation
OFF
Operation setting
during maintenance of
the compressor
AL30
Compressor
maintenance
Product operation
while the alarm is
being generated
OFF
Operation setting
during maintenance of
the dust-proof filter
AL40
Dust-proof filter
maintenance
Product operation
while the alarm is
being generated
OFF
Operation setting at a
time of operation
restoration after power
failure
AL41
Power stoppage
Product operation
while the alarm is
being generated
A.STP
Monitoring time for
maintenance of
dust-proof filter
AL40
*3
Dust-proof filter
maintenance
Alarm threshold
----
(500 h)
3:
This alarm does not occur on the product of water cooled type.