HRX-OM- T002
Chapter 5 Display and setting of various functions
HRS090 Series
5.8
Ready completion (TEMP READY) signal
5-19
5.8 Ready completion (TEMP READY) signal
5.8.1
Ready completion (TEMP READY) signal
This function sets a bandwidth for the set circulating fluid temperature
(range between the upper and lower limit temperatures) to notify the user by
communication that the circulating fluid temperature has reached the band
range.
The default setting of this function is “OFF”.
[Tips]
This function is available when contact input/output and serial communication
is being used. Refer to the Communications Operation Manual for further
details.
An example is shown below:
Set circulating fluid temperature:
20
o
C
READY bandwidth (range between
the upper and lower limit
temperatures):
±2
o
C
READY time:
60 seconds
Preparation for operation will be completed 60 seconds after the circulating
fluid temperature reaches the range of 18
o
C to 22
o
C.
Circulating set fluid 20
℃
READY TEMP 22
℃
READY TEMP 18
℃
READY band width
(
upper/lower temperature range
)
2
℃
READY band width
(
upper/lower temperature range
)
2
℃
Circulating set fluid
READY time
60
sec
Completion
of preparation
READY time
lower than
60
sec
Contact output
:
State generation output
Serial
:
ON output
Contact output
:
State not generation output
Serial
:
OFF output
Completion of preparation
(
TEMP READY
)