HRX-OM- T002
Chapter 9 Documents
HRS090 Series
9.1 Specifications
9-1
Chapter 9 Documents
9.1 Specifications
9.1.1
HRS090-A
-20
Table 9-1 Specifications [HRS090-A
-20
]
Model
HRS090-A
-20
Cooling method
Air-cooled refrigerated type
Refrigerant
R410A (HFC)
Quantity of refrigerant kg
1.15
Control method
PIDcontrol
Ambient temperature
1
o
C
5 to 45
Circulating
fluid
system
Circulating fluid
2
Tap water, Ethylene glycol aqueous solution 15%, Deionized water
Operating temperature range
1
o
C
5 to 35
Cooling capacity 50/60Hz
3
kW
8.0 / 9.0
Heating capacity
4
kW
1.7 / 2.2
Temperature stability
5
o
C
±0.5
Pump
capacity
Rated
flow
rate
50/60Hz (Outlet)
6
L/min
29 / 45
Maximum flow rate
50/60Hz
L/min
55 / 68
Maximum
lifting
height
m
50
Minimum operating flow rate
50/60Hz
7
L/min
29 / 45
Tank capacity
L
18
Circulating fluid outlet, circulating fluid
return port
Rc1 (Symbol F: G1, Symbol N: NPT1)
Drain port
Rc1/4 (Symbol F: G1/4, Symbol N: NPT1/4)
Wetted material
Stainless, Cupper(Heat exchanger brazing), Brass, Bronze, PTFE,
FKM, EPDM, PVC, NBR, POM, PE, PP, Carbon, Ceramic
Electric
system
Power supply
AC200/200-230V 50/60Hz 3phase
Allowable voltage fluctuation ±10% (No continuous voltage fluctuation)
Recommended
earth
leakage
breaker
8
Rated
current
A
30
Sensitivity
mA
30
Rated operating current
50/60Hz
5
A
16 / 18
Rated power consumption
50/60Hz
5
kW (kVA)
4.3 / 5.4 (5.5 / 6.0)
Sound level (F
ront 1m / Height 1m)
5
dB(A)
73
Accessory
Alarm cord list label 2pc.(English 1pc./Japanese 1pc.), Operation manual
2pc. (English 1pc./Japanese 1pc.),
Y strainer (40 meshes) 25A, Barrel nipple 25A
Anchor brackets 2pcs.(including M10 bolts 4pcs.)
9
Weight
(dry condition)
kg
Approx.136
1 Use 15% ethylene glycol aqueous solution if operating in a place where the circulating fluid temp. or ambient temperature is lower than
10
o
C
2 Use fluid in condition below as the circulating fluid.
Tap water: Standard of The Japan Refregeration And Air Conditioning Industry Association (JRA GL-02-1994)
15% ethylene glycol aqueous solution: diluted by tap water in condition above without any additives such as antiseptics.
Deionized water: Conductivity 1
μS/cm and higher (electrical resistivity 1MΩ
・
cm and lower)
3 (1)Operating ambient temp.: 32
o
C, (2)Circulating fluid : Tap water, (3)Circulating fluid temp.: 20
o
C, (4)Criculating fluid flow rate : Rated
flow rate, (5)Power supply: AC200V
4 (1)Operating ambient temp.: 32
o
C, (2)Circulating fluid : Tap water, (3) Circulating fluid flow rate : Rated flow rate, (4)Power supply:
AC200V
5 (1)Operating ambient temp.: 32
o
C, (2)Circulating fluid : Tap water, (3)Circulating fluid temp.: 20
o
C, (4)Heat load : Same as the cooling
capacity, (5)Circulating fluid flow rate: Rated flow rate, (6)Power : AC200V, (7) External piping length: Minimum.
6
When circulating fluid outlet port pressure = 0.5MPa.
7
Fluid flow rate to maintain the cooling capacity and to keep the circulating fluid outlet port puressure to 0.5MPa or less. If the actual flow
rate is lower than this, please install a bypass piping.
8
To be prepared by the customer. A specified earth leakage breaker is installed for option B [Earth leakage breaker] of each model.
9
The anchor brackets (including M10 bolts) are used for fixation with the skid when this product is packed. The anchor bolts are not
attached.