Adding Modbus to the MB-700
5.17
CCSM Block
Index
Parameter
DataType
Modbus Address
(Strategy = x)
Offset_SM = 200 * x
x = 0 ~ 24
Modbus Address
Strategy= 0
Offset_sm = 0
Modbus Address
Strategy= 1
Offset_Sm = 200
Modbus Address
Strategy = 2
Offset_Sm = 400
10
SCAN_STATUS
UInteger16 42001 + Offset_SM
42001
42201
42401
11.1
BVALUE[1]
Bool
2001 + Offset_SM
2001
2201
2401
11.2
BVALUE[2]
Bool
2002 + Offset_SM
2002
2202
2402
11.96 BVALUE[96]
Bool
2096 + Offset_SM
2096
2296
2496
12.1 IVALUE[1]
Integer32
42002-42003 +
Offset_SM
42002-42003
42202-42203
42402-42403
12.2 IVALUE[2]
Integer32
42004-42005 +
Offset_SM
42004-42005
42204-42205
42404-42405
12.8 IVALUE[8]
Integer32
42016-42017 +
Offset_SM
42016-42017
42216-42217
42416-42417
13.1 P_EU_VALUE_A[1] Float
42018-42019 +
Offset_SM
42018-42019
42218-42219
42418-42419
13.2 P_EU_VALUE_A[2] Float
42020-42021 +
Offset_SM
42020-42021
42220-42221
42420-42421
13.28 P_EU_VALUE_A[28]
Float
42072-42073 +
Offset_SM
42072-42073
42272-42273
42472-42473
14.1 P_EU_VALUE_B[1]
Float
42074-42075 +
Offset_SM
42074-42075
42274-42275
42474-42475
14.2 P_EU_VALUE_B[2]
Float
42076-42077 +
Offset_SM
42076-42077 42276-42277
42476-42477
14.28 P_EU_VALUE_B[28]
Float
42128-42129 +
Offset_SM
42128-42129 42328-42329
42528-42529
15.1 FVALUE[1]
Float
42130-42131 +
Offset_SM
42130-42131 42330-42331
42530-42531
15.2 FVALUE[2]
Float
42132-42133 +
Offset_SM
42132-42133 42332-42333
42532-42533
15.16 FVALUE[16]
Float
42160-42161 +
Offset_SM
42160-42161
42360-42361
42560-42161
Table 5.2 – Modbus Address Table of the MB-700 working as Modbus Slave
Using the Data Logger
Description
The MB-700 may store data Logs from a LC700 Data Logger Block (FIFO). So, during normal
reading of the Concentrate Data Logger it checks if there are data stored in the correspondent slave.
In case there are data stored it will read these data and clear the log buffer of the slave.
Configuration
First create a FIFO Block in the LC700. In the SYSCON configuration it is possible to include as
many Concentrate Data Logger Blocks as it is required. To insert a CCDL Block just proceed like it
was done to the other MB-700 Blocks.
NOTE
: the amount of CCDL blocks depends on the FIFO size defined in the LC700 (FIFO Size).
Each CCDL supports up to 280 data samples. For example, if the FIFO size is 1000 registers and
the data type is integer (percentage) so it is necessary: 1000/280 = 4 CCDL blocks.
Summary of Contents for MB-700
Page 1: ...M B 7 0 0 M E...
Page 4: ...MB 700 User s Manual IV...
Page 8: ...MB 700 User s Manual VIII...
Page 14: ...MB 700 User s Manual XIV...
Page 18: ...MB 700 User s Manual 1 4...
Page 30: ...MB 700 User s Manual 2 12...
Page 56: ...MB 700 User s Manual 4 18...
Page 76: ...MB 700 User s Manual 5 20...
Page 98: ...MB 700 User s Manual A 4...
Page 105: ...Cabling B 7 Dimensions Figure B 8 Dimensions...
Page 106: ...MB 700 User s Manual B 8...
Page 114: ...MB 700 User s Manual D 2...