MB-700 – User’s Manual
5.4
Figure 5.4 – Configuration Screen CCCF Block
The following parameters must be adjusted:
9
BAUD_RATE: Adjust to 57600.
9
BYPASS_DIRECTION: TCP to Serial.
9
NUMBER_RETRANSMISSIONS: Choose "3".
9
TIMEOUT: "1000" (1000 ms).
9
MODE_BLK: Select "Auto".
9
DEVICE_ADDRESS: Make sure that in the MODBUS network there is not any other address
with the number shown for this parameter. Default: 247.
9
ON_APPLY: Set this parameter for “Apply”.
To have best visualization, rename the blocks which have created. Right click the Block 1(where a
RESOURCE block must have added). A menu will open.
•
User should select the Attributes option and change the block tag according to the
convenience. The same procedure might be done with the other blocks.
•
At the end, a table like below must appear on Syscon.