MB-700 – User’s Manual
4.4
Parameters
Idx
Parameter
Data Size
(length)
Valid Range/
Options
Default
Value
Unit
Store /
Mode
Description
1
ST_REV Unsigned16
0
None
S
2
TAG_DESC OctString(32)
Spaces
Na
S
3 STRATEGY Unsigned16 0
None
S
4
ALERT_KEY
Unsigned8
1 to 255
0
None
S
5
MODE_BLK
DS-69
O/S
Na
S
See Mode Parameter
6
BLOCK_ERR
Bitstring(2)
E
D / RO
7 REDUNDANCY_ROLE
Unsigned8
Not
used Main
E S
It specifies the preferable MB-700 to
be Active, when there is
redundancy.
8 REDUNDANCY_STATE
Unsigned8
Not
used Standby
E
D/RO
It shows which MB-700 is Active
and which MB-700 is in Standby
mode.
9
BAD_COMM
Boolean
Not used
TRUE
E
D / RO
It indicates if any slave Modbus
device scanned by MB-700 is not
communicating.
10
BAD_COMM_STANDBY
Unsigned8
Not used
TRUE
E
D / RO
It indicates if the Standby is not able
to communicate with a slave device.
11 CHECK_COMM_STANDBY
Unsigned8
0-255
0
Na
S
This parameter is configured to
Standby, if the communication test
between the slave equipment was
performed in TCP.
0: Disables the test.
1 – 255: Enables the test and
defines the time interval, in
seconds, between each test.
12 DEVICE_ADDRESS
Unsigned8
1-247
247
E S
Define the device address in the
Modbus network when acting as a
slave.
13 SLAVE_ADDRESSES
DS-263
S
IP number and corresponding
device address of slave device,
when accessed through Ethernet
TCP/IP.
14 BAUD_RATE
Unsigned8
0:110, 1:300,
2:600, 3:1200,
4:2400, 5:4800,
6:9600, 7:19200,
8:38400,
9:57600,
10:115200
9600 E S
It defines the baud rate for serial
ports.
15 STOP_BITS
Unsigned8
0:1,
1:2
1
E
S
It defines the number of stop bits for
serial ports.
16 PARITY
Unsigned8
0:None, 1:Even,
2:Odd.
Even E S It defines the parity for serial ports.
17 TIMEOUT
Unsigned16
0-65535
1000
ms
S
Time to wait a response from a
slave after sending the command in
the serial ports.
18 RTS_CTS_TIMEOUT
Unsigned16
0-65535
0 ms S
Specify the maximum time waiting
for CTS become active after setting
RTS in the serial ports.
19
NUMBER_RETRANSMISSION
S
Unsigned8 0-255 1
S
Number of retransmission if MB-700
doesn’t receive response from
slave.
20
SUPERVISION_OFF_DUTY Unsigned16
0-65535
0 ms S
Time between supervision
commands. The zero value
indicating that the OFF_DUTY is
disabled.
21 CONTROL_OFF_DUTY
Unsigned16
0-65535
0 ms S
Time between control commands.
The zero value indicating that the
OFF_DUTY is disabled.
Summary of Contents for MB-700
Page 1: ...M B 7 0 0 M E...
Page 4: ...MB 700 User s Manual IV...
Page 8: ...MB 700 User s Manual VIII...
Page 14: ...MB 700 User s Manual XIV...
Page 18: ...MB 700 User s Manual 1 4...
Page 30: ...MB 700 User s Manual 2 12...
Page 56: ...MB 700 User s Manual 4 18...
Page 76: ...MB 700 User s Manual 5 20...
Page 98: ...MB 700 User s Manual A 4...
Page 105: ...Cabling B 7 Dimensions Figure B 8 Dimensions...
Page 106: ...MB 700 User s Manual B 8...
Page 114: ...MB 700 User s Manual D 2...