MB-700 – User’s Manual
4.14
D - Supervision Status
1 - Parameter COMM_STATUS
This parameter indicates if the communication between slaves was established properly. If the
corresponding bit is in logic level 1, it means there was an error during writing/reading of the
respective parameter.
Bit
Variable
0
BAD COMM MOD_VAR_IN1
1
BAD COMM MOD_VAR_IN2
2
BAD COMM MOD_VAR_IN3
3
BAD COMM MOD_VAR_IN4
4
BAD COMM MOD_VAR_IN_D1
5
BAD COMM MOD_VAR_IN_D2
6
BAD COMM MOD_VAR_IN_D3
7
BAD COMM MOD_VAR_IN_D4
8
BAD COMM MOD_VAR_OUT1
9
BAD COMM MOD_VAR_OUT2
10
BAD COMM MOD_VAR_OUT3
11
BAD COMM MOD_VAR_OUT4
12
BAD COMM MOD_VAR_OUT_D1
13
BAD COMM MOD_VAR_OUT_D2
14
BAD COMM MOD_VAR_OUT_D3
15
BAD COMM MOD_VAR_OUT_D4
Table 4.4 – Bit / Parameter Status
Parameter Status
Each input or output parameter has a corresponding status. The slave device through configuration
of the MODBUS_ADDRESS_OF_STATUS might update this status. This happens only if the slave
device has a status (this status follows the
F
OUNDATION
TM
Fieldbus
standard). See more details of
how to set this status in the Function Blocks manual. If the MODBUS_ADDRESS_OF STATUS
parameter is not configured, the CCCM Block automatically updates the status to “Good Non
Cascade” when the communication with slave is OK or “Bad No Communication with last value” and
“Non-Specific”, if communication fails.
Parameters
Idx
Parameters
Data Type
(Length)
Valid
Range/
Options
Default
Value
Unit
Store /
Mode
Description
1 ST_REV Unsigned16
0
None
S
2 TAG_DESC
OctString(32)
Spaces
Na
S
3 STRATEGY Unsigned16
0 None
S
4
ALERT_KEY
Unsigned8
1 to 255
0
None
S / OOS
5
MODE_BLK
DS-69
O/S
Na
S
See Mode Parameter
6
BLOCK_ERR
Bitstring(2)
E
D / RO
7
COMM_STATUS
Bitstring(2)
0
E
D / RO
Indicate if communication from slave is good or not
(each bit corresponds to a Modbus variable).
8
IN1
DS-65
N
Analog input 1
9
EU_ADDRESS_IN1
DS-266
S / OOS
Information to generate constants A and B em
equation Y=A*X+B plus the addresses in a slave
device.
10
IN2
DS-65
N
Analog input 2
11
EU_ADDRESS _IN2
DS-266
S / OOS
Information to generate constants A and B em
equation Y=A*X+B plus the addresses in a slave
device.
12
IN3
DS-65
N
Analog input 3
Summary of Contents for MB-700
Page 1: ...M B 7 0 0 M E...
Page 4: ...MB 700 User s Manual IV...
Page 8: ...MB 700 User s Manual VIII...
Page 14: ...MB 700 User s Manual XIV...
Page 18: ...MB 700 User s Manual 1 4...
Page 30: ...MB 700 User s Manual 2 12...
Page 56: ...MB 700 User s Manual 4 18...
Page 76: ...MB 700 User s Manual 5 20...
Page 98: ...MB 700 User s Manual A 4...
Page 105: ...Cabling B 7 Dimensions Figure B 8 Dimensions...
Page 106: ...MB 700 User s Manual B 8...
Page 114: ...MB 700 User s Manual D 2...