MB-700 – User’s Manual
4.8
4 - F_VALUE Parameter:
Through this parameter user will visualize float variables addressed by F_ADDRESS_i. The block
supports up to 16 float variables that can be mapped for supervision of the Modbus slave device.
C - Supervision Status
1 - SCAN_STATUS Parameter:
Status parameter of the scan done by the MB-700 in the communication with serial slave devices.
BIT
Message
Description
0
Last write message Failed
When the value set for NUMBER_RETRANSMISSIONS is reached,
and if the MB-700 didn’t get to write data properly, the value
SCAN_STATUS will indicate “Last write message Failed”.
1
Scan failed
When the value set on NUMBER_RETRANSMISSIONS is reached
and the MB-700 didn’t get an answer from the serial slave, the value
of SCAN_STATUS will indicate “Scan Failed’.
2
Using configurable view
If user set SCAN_BEHAVIOR equal to one and the communication
with the slave is done using View the scan status will indicate “Using
Configurable View”
3
Scan Stopped
Indicates if the scan stopped for any reason.
Table 4.2 – Description of the Status Bits
Parameters
Idx
Parameter
Data Type
(Length)
Valid Range/
Options
Default
Value
Unit
Store/
Mode
Description
1
ST_REV Unsigned16
0
None
S
2
TAG_DESC OctString(32)
Spaces
Na S
3 STRATEGY Unsigned16
0 None
S
4
ALERT_KEY
Unsigned8
1 to 255
0
None
S
5
MODE_BLK
DS-69
O/S
Na
S
See Mode Parameter
6
BLOCK_ERR
Bitstring(2)
E
D / RO
7
SLAVE_ADDRESS
Unsigned8
0 to 255
2
S /
OOS
Address of slave device to be scanned.
8 SERIAL_PORT Unsigned8
1 : P1
2 : P2
1 1
S /
OOS
Serial port number where the slave device
is connected.
9 SCAN_BEHAVIOR Unsigned8
0 : Use Config
View
1 : Not Use
Config View
0 0
S /
OOS
Define if will use the configured view to
scan the device or not.
10 SCAN_STATUS Bitstring(2)
See Scan_Status
bitstring
description
0
E
D / RO
Indicate the communication status with the
slave device.
11 BVALUE 96
Boolean
FALSE
N
Boolean value scanned from slave device
12 IVALUE 8
Interge32
0 N
Integer value scanned from slave device.
13 P_EU_VALUE_A
28
Float
0
N
Percent to EU value scanned from slave
device
14 P_EU_VALUE_B
28
Float
0
N
Percent to EU value scanned from slave
device
15 FVALUE
16
Float
0.0 N
Float value scanned from slave device.
16 B_ADDRESS1 Unsigned16
65535
S /
OOS
Modbus address to locate boolean
variable
… …
…
… …
…
…
…
111 B_ADDRESS96 Unsigned16
65535
S /
OOS
Modbus address to locate boolean
variable
112 I_ADDRESS1
DS-264
S /
OOS
Modbus address to locate integer variable
and length.
… …
…
… …
…
…
…
119 I_ADDRESS8
DS-264
S /
OOS
Modbus address to locate integer variable
and length.
Summary of Contents for MB-700
Page 1: ...M B 7 0 0 M E...
Page 4: ...MB 700 User s Manual IV...
Page 8: ...MB 700 User s Manual VIII...
Page 14: ...MB 700 User s Manual XIV...
Page 18: ...MB 700 User s Manual 1 4...
Page 30: ...MB 700 User s Manual 2 12...
Page 56: ...MB 700 User s Manual 4 18...
Page 76: ...MB 700 User s Manual 5 20...
Page 98: ...MB 700 User s Manual A 4...
Page 105: ...Cabling B 7 Dimensions Figure B 8 Dimensions...
Page 106: ...MB 700 User s Manual B 8...
Page 114: ...MB 700 User s Manual D 2...