MB-700 – User’s Manual
4.2
Ethernet
PC without
Ethernet Adapter
LC700
RS-232
MB-700
Data flow direction:
Serial to TCP
MB-700
Data flow direction:
TCP to Serial
RS-485
DFI302
MB-700
MB-700
Figure 4.2 – MB-700 Configuration Example as Serial Slave (MB-700 Communication with
Work Station) and Serial Master (MB-700 Communication with LC700)
NOTE
For this scenario, MB-700 does not support CCSM and CCCM Blocks.
MODBUS Addresses
User must attribute a Modbus address to the MB-700. However this address must be unique in the
Modbus networks where the MB-700 is connected through Ethernet or serial ports. In this case, user
must set the DEVICE_ADDRESS parameter. The default value for this parameter is 247.
Configuring the Serial Media
In applications where the serial port of MB-700 is used, user must set the following parameters:
1 - Rate of transference of the serial ports
It is possible to select the baud rate of data in the serial ports. They may be set through the
parameter BAUD_RATE. It allows the selection among the following baud rates:
9
0: 100 bps
9
1: 300 bps
9
2: 600 bps
9
3:
1200
bps
9
4:
2400
bps
9
5:
4800
bps
9
6:
9600
bps(default)
9
7: 19200 bps
9
8: 38400 bps
9
9: 57600 bps
9
10: 115200 bps
2 - Parity
Parameter PARITY defines the type of parity to the serial ports.
9
0: No parity
9
1: Even Parity (default)
9
2: Odd parity
3 – Timeout and Number of retransmissions
Timeout
: time waited for an answer from a slave, after a message has been sent through one of the
serial (P1 or P2) or Ethernet ports. The TIME_OUT parameter can change between 0 and 65535
milliseconds, and its default value is 1000. This parameter is directly connected to the
NUMBER_RETRANSMISSIONS parameter.
Number of retransmissions
: number of times the MB-700 will retry to communicate with the slave
device after not getting a reply. The time waited for this answer is set in the TIME_OUT parameter.
The number of retransmissions is chosen through the NUMBER_RETRANSMISSIONS parameter.
User may select a value in the range 0 to 255 to this parameter, and its default value is 1.
Summary of Contents for MB-700
Page 1: ...M B 7 0 0 M E...
Page 4: ...MB 700 User s Manual IV...
Page 8: ...MB 700 User s Manual VIII...
Page 14: ...MB 700 User s Manual XIV...
Page 18: ...MB 700 User s Manual 1 4...
Page 30: ...MB 700 User s Manual 2 12...
Page 56: ...MB 700 User s Manual 4 18...
Page 76: ...MB 700 User s Manual 5 20...
Page 98: ...MB 700 User s Manual A 4...
Page 105: ...Cabling B 7 Dimensions Figure B 8 Dimensions...
Page 106: ...MB 700 User s Manual B 8...
Page 114: ...MB 700 User s Manual D 2...