Protection
Protection Module Configuration with IMx-M Manager
2 - 178
SKF Multilog On-Line System IMx-M
User Manual
Figure 2 - 147.
Getting the Sensor Parameters by Calculation Help.
After pressing the button "
Calculate and set Sensitivity and Zero Level
" in the
Calculation Help box, new values are automatically calculated and set for the
Sensitivity
and
Zero level
. The warning symbol disappears after the parameter
values are set.
The value of the
Sensitivity
is changed from 1 to 0.16 mA/% in order to give a
reading of 0% for 4mA and 100% for 20mA.
The
Zero level
is in this case unchanged from its default value.
The
Sensor OK
levels are configured to 1.8 and 22 mA to give a slight margin to
the sensor maximum output (20mA) and minimum output (4mA).