Technical Data
Analog Measurement - Protection
SKF Multilog On-Line System IMx-M
7 - 3
User Manual
Up to 96 configurable relay outputs (Disarm, Alert, Danger, Not OK and Voting)
Slot status circuit fault (CF) relay output
Slot disarm (Dis) relay output
Analog Measurement - Protection
16-bit AD conversion enabling continuous transient capture (no gain or AC/DC
switching required)
True simultaneous sampling of all 64 channels (no multiplexing)
Simultaneous sampling of different channels with different sampling rates
Frequency range: from DC to 10 kHz
Dynamic range: 90 dB
Signal to noise ratio: 90 dB
Cross-talk rejection: 100 dB
Accuracy amplitude: ±2% (Velocity 1 000 to 10 000 Hz, ±3%)
Typical accuracy amplitude < ±1% of API 670 defined full scale range.
Note
: Filters ±0,5 dB in passband
Accuracy measurement type Other:
±1% for 0-10 VDC input
±2,9% for 4-20 mA input
Note
: Accuracy ±1% (±2,9% for 4-20 mA) is only fulfilled if the complete 0-10 V or
complete 4-20 mA range is utilized to reflect the configured full scale.
Digital Measurement
–
Protection
Frequency range: 0,1 Hz to 7,5 kHz (Eddy current probe low frequency limit 2 Hz)
Required pulse width: > 25 µs for electrical positive, > 67 µs for electrical negative
Accuracy frequency: 0,05% of measurement value (typically 0,01% up to 2,5 kHz)
Peak speed detection
Relay - Protection
Maximum switching voltage: up to 60 V DC, 30 V RMS/42,4 V peak
Maximum switching capacity: 60 W, 62,5 VA
Maximum switching current: max 2 A peak, max 1 A continuously
Mechanical endurance: typical 10
8
operations
Electrical endurance: minimum 10
5
operations at maximum rating
Category of protection: hermetically sealed (RTV)