Hardware
Hardware Configuration
SKF Multilog On-Line System IMx-M
4 - 25
User Manual
Table 4-7: RS485 Modbus termination DIP switch settings for L1, L2.
RS485 Modbus Termination DIP Switch Settings
L1
L2
DIP Switch Setting
1234
OFF
OFF
0000
ON
OFF
1000
OFF
ON
0100
ON
ON
1100
The location of RS485 Modbus termination DIP switch is found in
4-20 mA Output
Each CMM + PRM slot offers 16 4
–
20 mA Outputs. This connection is used for sending
protection measurement values from the CMM + PRM slot to the distributed control
system (DCS
)
. Each 4
–
20 mA output can be configured to reflect the value of analog
channel measurement or related combined measurement.
Each 4
–
20 mA Output is updated every 640 ms.
The values are related to the scale setup in 4-20 mA Outputs configuration via IMx-M
Manager. 4 mA will correspond to the minimum scale value and 20 mA to the
maximum scale value with a linear scaling between those values.
Examples are shown below.
Scale configured to 0 to 10 will give
4 mA = 0
20 mA = 10
Scale configured to -10 to 30 will give
4 mA = -10
8 mA = 0
20 mA = 30
A cable fault will result in less than 3 mA output.
Selection of the output voltage is done via a jumper (JMP2). The jumper (JMP2) is
located on the condition monitoring module as shown in the
DIP Switch and Jumper on Condition Monitoring Module
drawing. The configuration of jumper is shown below.