Protection
Protection Module Configuration with IMx-M Manager
SKF Multilog On-Line System IMx-M
2 - 97
User Manual
Figure 2 - 73.
Adding a New Rack to the Hierarchy.
This dialog shows a representation of an empty IMx-M rack with two power supply units
fitted and fault detections enabled.
Rack Name
The first task is to assign a name to this rack. Given that each rack is a physical item
mounted in a geographical area, the name chosen should always be an easier reference
f
or future use (E.g. “MOL ROOM LOWER RACK”).
Configure System setup
The next task is to effectively “build” this virtual rack by populating each of the four
empty CMM + PRM slots and then adding a relay module to its associated CMM + PRM
slot. However as the rack can only hold a maximum of three relay modules, these can
only be associated with the first three CMM + PRM slots in the rack.